Jupiter Evolving SIGCOMM ’22 SciPy HiGHS · Cloudflare Pages
Google’s Optical Circuit Switched (OCS) + SDN Direct-Connect Datacenter Simulator
Talk Timer 12:00
Speed & Capacity Evolution 5× 40G → 100G → 200G+ live refresh
Fabric Capex (vs. Clos Baseline) 70% (-30%) 62% amortized across generations
Fabric Power (vs. Clos Baseline) 59% (-41%) Spine deleted · Circulators 0W
Fleet Avg Path Stretch 1.4 60% direct · 40% 1-hop (Clos = 2.0)
OCS Rewiring Speedup 9.6× / 3.3× Median / Mean vs. manual patch panel

Live 8-Block Mixed Datacenter: Click Any Block to Upgrade Speed!

See how a pre-built Day-1 40G Clos spine bottlenecks newer 100G/200G blocks, while Direct-Connect OCS + ToE unlocks their bandwidth.

Solved in -- ms

Interactive Cost & Power Model (§6.5, Fig. 14)

Toggle Jupiter’s architectural pillars live against the conventional Clos + Patch Panel baseline.

Slide Plot: Act 1 (Click to Zoom Full-Screen)

Act 1 Clos vs Direct Connect Plot

LIVE SciPy MILP Solver: Heterogeneous ToE “Demultiplexer” (§4.5, Fig. 9)

Drag traffic demands below — the Python backend re-solves the joint integer link-allocation + routing MILP live!

MILP: -- ms
UNIFORM MESH (250/250) --
LIVE ToE MILP SOLUTION --
Demand A ↔ B55 Tbps
Demand A ↔ C25 Tbps
Demand B ↔ C15 Tbps
Block C Speed100G

Multi-Fabric Sweep (§6.2, Fig. 12)

Throughput normalized to a perfect high-speed spine (1.0) & optimal stretch across 6 heterogeneous speed mixes.

Fabric Mix Unif TP ToE TP Unif Str ToE Str

Slide Plot: Act 2 (Click to Zoom Full-Screen)

Act 2 ToE Demux and Multi-Fabric Plot

LIVE LP: Variable Hedging Burst Test (§4.4, Fig. 8)

Constraint: x_p ≤ D · C_p / (B · S) · Pred: A↔B=2, A↔C=2

LP: -- ms
Spread S (0.05 Greedy MCF ↔ 1.00 VLB) 0.65
Actual Burst on A ↔ B (Predicted = 2.0) 4.0 (2.0×)

2-VRF Loop-Free 1-Hop Transit (§4.3)

Why single-table destination routing loops when A→B→C and B→A→C coexist.

LIVE Fig. 13 Time-Series: Watch Your Spread S Track 30s Traffic!

Switch between Bursty Fabric D vs. Stable Fabric G (§6.3) and drag Spread S on the left to re-simulate live.

Slide Plot: Act 3 (Click to Zoom Full-Screen)

Act 3 TE Variable Hedging Plot

LIVE Rewiring Player: Adding Blocks C & D (§5, Fig. 11 & Fig. 18)

Step through failure-domain increments — compare Single-Shot outage (33.3%) vs. Hitless Drain (≥83.3% online).

LIVE 4-Failure-Domain OCS Kill Switch (§3.2, §4.2, Fig. 6)

Click any OCS failure domain to simulate a power/control outage — real SciPy LP re-evaluates residual throughput live!

LP: -- ms
LIVE RESIDUAL THROUGHPUT
100.0%
Jupiter 1-Domain SLO: ≥ 75.0%
Orion SDN Control CONNECTED
OCS mirrors stay locked on control loss → 100% dataplane alive!
Generated Optical Engine OpenFlow Rules (§4.2)

Slide Plot: Act 4 (Click to Zoom Full-Screen)

Act 4 Tier 2 Rewiring and Failure Domains Plot

All 4 Generated Paper Plots (Click Any Chart to Full-Screen Zoom)

Every figure below was freshly generated by your Python solvers in outputs/.

Fig 1 — Clos Derating & Cost/Power (§1–2, §6.5)
Fig 1
Fig 2 — ToE Demultiplexer & Multi-Fabric (§4.5, §6.2)
Fig 2
Fig 3 — TE Variable Hedging Time-Series (§4.4, §6.3)
Fig 3
Fig 4 — Hitless Live Rewiring & 4 Failure Domains (§3.2, §5)
Fig 4

12-Minute Stage Cue Card & Q&A Crib Sheet

Keys: 1–5 switch tabs · T toggle projector light theme

0:00–3:00 · Act 1: The Clos Trap & Optical Hardware

Click blocks on Tab 1 to upgrade them to 200G — watch Clos flatline at 20T (derated!) while OCS unlocks full speed. Mention Palomar 136×136 MEMS (850nm camera servo), 0W passive circulators (halve OCS ports, bidirectional constraint), CWDM4 interop, and −30% capex / −41% power.

3:00–6:00 · Act 2: Topology Engineering Demultiplexer

On Tab 2, drag A↔B or A↔C sliders live and watch SciPy MILP re-discover Google’s 300/200 split with 5T transiting via B (turning B into a 200G→100G demux!). Note cadence: ToE runs every few weeks today, but large ML jobs will push it faster.

6:00–9:30 · Act 3: Variable Hedging & 2-VRF Routing

On Tab 3, trigger the A↔B=4 burst at S=0.05 (MLU=1.00!) then slide S up to watch MLU drop to 0.75. Flip Fabric D (bursty, loves high S) vs. Fabric G (stable, loves low S), and toggle 2-VRF isolation to show loop-free 1-hop transit.

9:30–13:00 · Act 4 [Tier 2]: 4 Failure Domains & Zero-Loss Rewiring

Press ▶ Play on Tab 4 to step through Fig. 11 (≥83.3% online vs. Single-Shot 33.3% crash). Click “Kill Domain 1” to prove ≥75% residual throughput live, and click “Disconnect Orion” to demonstrate fail-static OCS mirrors + generated OpenFlow rules!

Rapid-Fire Q&A Cheat Answers

Why does Direct-Connect match Clos throughput? Gravity Model (RMSE 0.05) + Theorem 2 + NPOL skew (<10% quiet transit blocks).
What happens on OCS power loss? Drops links (unlike fail-static control loss), bounded to 1/32 per rack & ≤25% per power/control domain.
New bottleneck after 9.6× OCS speedup? Operations workflow software jumped from 4.7% → 37.7% of critical path (Table 2).